DC1500V POWER SURGE PROTECTOR
DC1500V POWER SURGE PROTECTOR
15-SP07M-DC15
Add to inquiry box
Production information
DC1500V POWER SURGE PROTECTOR
IEC/ EN 61643-31 CERTIFIED
IEC/ EN 61643-31 CERTIFIED


- High discharge capacity, quick response, individually plugged modules
- Fast response time, din-rail installation
- Double thermal disconnection devices, provide more reliable protection
- Green window means normal, red means defect, need to change module
- Remote signaling contact optional
- T2 surge protection
- IEC/ EN 61643-31 certified
| Model | 15-SP07M-DC15 |
| Test standard | IEC/EN 61643-31 |
| SPD type | T2 / Class II |
| Max. PV voltage [ Uc pv ] | 1500V DC |
| Nominal discharge current (8/20µs) | 20kA |
| Maximum discharge current(8/20µs) | 40kA |
| Poles | 3P |
| Voltage protection level Up pv | 5.6kV |
| Response time Ta | 25ns |
| Connection wire specification | 4mm2(L/N); 6mm2(PE) |
| Mounting | 35mm Din Rail |
| Matched fuse or circuit breaker | 32A |
| Type of remote signaling contact (Optional) |
C+NC: Normally closed C+NO: Normally open C: Common contact |
| Max. Voltage/Current for remote signaling | 1A /2A /3A 125V AC |
| Wiring for remote signaling | 1.5mm2 max. |
| Operating temperature | -40°C to +80°C |
| Shell material | UL94-V0 fireproof material |

FEATURES
- High discharge capacity, quick response, individually plugged modules
- Fast response time, din-rail installation
- Double thermal disconnection devices, provide more reliable protection
- Green window means normal, red means defect, need to change module
- Remote signaling contact optional
- T2 surge protection
- IEC/ EN 61643-31 certified
SPECIFICATION
| Model | 15-SP07M-DC15 |
| Test standard | IEC/EN 61643-31 |
| SPD type | T2 / Class II |
| Max. PV voltage [ Uc pv ] | 1500V DC |
| Nominal discharge current (8/20µs) | 20kA |
| Maximum discharge current(8/20µs) | 40kA |
| Poles | 3P |
| Voltage protection level Up pv | 5.6kV |
| Response time Ta | 25ns |
| Connection wire specification | 4mm2(L/N); 6mm2(PE) |
| Mounting | 35mm Din Rail |
| Matched fuse or circuit breaker | 32A |
| Type of remote signaling contact (Optional) |
C+NC: Normally closed C+NO: Normally open C: Common contact |
| Max. Voltage/Current for remote signaling | 1A /2A /3A 125V AC |
| Wiring for remote signaling | 1.5mm2 max. |
| Operating temperature | -40°C to +80°C |
| Shell material | UL94-V0 fireproof material |
DIMENSION

VIDEO